Talk to an Expert !
Live chat or (888) 461-1112

S8910U3000 : Resideo Honeywell S8910U3000 Universal Hot Surface Ignition Module

  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
  • Photo of S8910U3000
Resideo Logo
$21888
In-Stock - Ships Immediately


 

SKU: S8910U3000
Compare at: $366.66
You Save: 41%

Universal hot surface ignition module replaces multiple field installed hot surface ignition modules supplied by Resideo Honeywell, White-Rodgers, Robertshaw and Johnson. Uses a 120 VAC igniter. Includes cross reference, instructions, and accessories for easy replacement.

Replaces over 800 White-Rodgers, Robertshaw and Resideo Honeywell hot surface ignition models.
For 120 Vac (up to 5.0A) surface igniter (Norton 201/271 or equivalent).
S8910U 3000 Series has LED status indicator and microammeter ports for easy trouble shooting
For local (single rod) or remote (dual rod) rectification type flame sensing.
Contains easy-to-use cross reference and instructions plus the accessories required to replace the existing hot surface ignition module.
Provides one or three ignition trials (four-second or seven-second trials) per call for heat.
Field selectable number of ignition trials and trial time based on unit being replaced.
Igniter warm up time: 7 (12 seconds second and third trial), 17 (27 seconds second and third trial), 34, or 45 seconds


Product Specifications

  Ambient Temperature Range (C): -40 C to +79 C
  Ambient Temperature Range (F): -40 F to +175 F
  Between Trial Time (sec): (2) 96 sec (32 Seconds Prepurge and 64 seconds interpurge)
  CSA Approved: Design Certified
  Dimensions (in): 5 1/4 in. high x 4 1/16 in. wide x 1 15/16 in. deep
  Dimensions (mm): 133 mm high x 103 mm wide x 49 mm deep
  Electrical Rating (amp): 24 Vac
  Flame Failure Response Time (sec): 1.5 sec.
  Flame Sense: Single Rod or Two Rods
  Frequency: 50 Hz; 60 Hz
  Ignition Sequence: The number of trials for ignition and trial time is determined by the dip switch selection.
  Ignition Source: Line Voltage (120 VAC) Hot Surface Element (Norton Model 201 or 270)
  Ignition System Type: Direct Hot Surface Ignition
  Ignition Trials To Lockout: 1 or 3
  Ignition Trial Time (sec): 4 sec. or 7 sec.
  Lockout Timing: 4 sec. or 7 sec.
  Maximum Valve Load @ 24 Vac (Amps): 2A
  PrePurge: 32 seconds
  Type of Gas: Natural or LP
  Typical Gas Control: VR8205, VR8305

Product Downloads
  Product Specifications
  Installation Instructions

21N34 85267647489
B0009784IY B013JU93YG
S8910U1000 S8910U3000/U